Skip to main content
GAS ELECTRO-VALVES N.C. 6 bar Dimensions DN65 - DN100

Produced by:

P.IVA 03124320171
via E.Fermi, 98 - 25064 Gussago (BS), Italy
Tel.+39 030 3730218
info@gecasrl.it

Tags

GAS ELECTRO-VALVES N.C. 6 bar Dimensions DN65 - DN100

GAS GAS solenoid valves have been designed to be combined with any gas detection system or carbon monoxide. Shut off the main outlet when an emergency situation is detected.
They have been installed at the gas piping and connected with a gas detector. Interrupt the gas flow in a danger situation.
The electro-valve is normally located after a filter, upstream of the regulation apparatus and preferably outside the measurement zone. It has been installed with the arrow stamped on the body turned towards the user appliance. lenoid valve unscrew the protection cap and screw it down in the apposite threading and pull up.

Standard Specifications

Power supply: 230 Vca – 24 Vcc/Vca – 12 Vcc/Vca
Body: aluminium
Working temperature: -15°C / +70°C
Closing time: < 1 sec
Max pressure: 6 bar (2 bar for DN125 and DN150)
Protection level: IP65
Connections: flanged UNI 2223
Weight: DN65=7,0Kg DN80=7,5Kg DN100=9,5Kg

Type
Connection
Flow
Power
A mm
B mm
power supply
VR946/12
DN65 2” ½
170 (mc/H)
16 W
350
348
12Vcc
VR946
DN65 2” ½
170 (mc/H)
15 W
350
348
230Vac
VR947/12
DN80 3”
170 (mc/H)
16 W
350
348
12Vcc
VR947
DN80 3”
170 (mc/H)
15 W
350
348
230Vac
VR948/12
DN100 4”
280 (mc/H)
16 W
350
348
12Vcc
VR948
DN100 4”
280 (mc/H)
15 W
350
348
230Vac

Gas solenoid Valves Pressure Drop table

Do you need further informations?

Get in touch with us

If you have not found the product or service you want, or if you need a tailor-made project contact us now! We are happy to help.