Gas Regulator with Slam Shut valve
The gas pressure regulators are spring-loaded gas regulators with balanced plug, diaphragm command and contrast action by spring, suitable for low and medium pressure. Regulator and shut-off device are supplied with internal sensing lines. Both regulator and shut-off device are preset for connection to an external sensor line by the customer. They are widely used either in civil or industrial plants, using natural gas or LPG or non-corrosive gas. This regulator is equipped with an integrated slam shut valve that closes in case pressure goes over or/and under the set point limit.
Standard Specifications
Pmax inlet max – 5 bar
Setting outlet 5 – 300 mbar – Standard spring supplied 10 – 27 mbar – Other spring on request
UPSO 10 - 60 mbar - Standar spring supplied 5 - 14 mbar
OPSO 150 - 700 mbar - Standar spring supplied 150 - 250 mbar
Others configuration on request
Inlet - Outlet Connection Thread gas 1 1⁄4” 11⁄2” - ISO 228 connection DN32 DN40 DN50 - Sliding Aluminium flange PN10
Test point Inlet / outlet on request – Test point 1/8” NPT
Working Temperature - 20 °C – + 60 °C
Use Not aggressive gases of three families – Natural Gas – LPG – Town Gas
Complete Body Die – Cast Aluminium Gd – AlSi12Cu - EN AB 46100
Diaphragms NBR 60Sh – DvGW EN 549
Plastic components White POM / Pa 66 + 25% Gf
Approval UNI EN 88-1:2008 / PED
Options
Color: White Range: 5 - 14 mbar
Color: Yellow Range: 6 - 22 mbar
Color: Neutral Range: 10 - 27 mbar
Color: Red Range: 28 - 70 mbar
Color: Black Range: 60 - 130 mbar
Color: Blue Range: 120 - 300 mbar
If you want test point in and out pls add code TPIO at the end of the code.
Gas Regulator with Slam Shut valve
images/zoo/RG-SSV.jpg
<p>The gas pressure regulators are spring-loaded gas regulators with balanced plug, diaphragm command and contrast action by spring, suitable for low and medium pressure. Regulator and shut-off device are supplied with internal sensing lines. Both regulator and shut-off device are preset for connection to an external sensor line by the customer. They are widely used either in civil or industrial plants, using natural gas or LPG or non-corrosive gas. This regulator is equipped with an integrated slam shut valve that closes in case pressure goes over or/and under the set point limit.</p>
Gas regulators
// Code example
<div id="myid" class="myclass" hidden>
Lorem ipsum <strong>dolor</strong> sit amet, consectetur adipiscing elit.
</div>
Type | dimensions | Description | Pressure |
---|---|---|---|
RG015-HC-5B-SSV | 1/2" | Gas Regulator with SSV | 5 Bar |
RG015-HC-SSV | 1/2" | Gas Regulator with SSV | 500 mBar |
RG020-HC-5B-SSV | 3/4" | Gas Regulator with SSV | 5 Bar |
RG020-HC-SSV | 3/4" | Gas Regulator with SSV | 500 mBar |
RG025-HC-5B-SSV | 1" | Gas Regulator with SSV | 5 Bar |
RG025-HC-SSV | 1" | Gas Regulator with SSV | 500 mBar |
RG032-SSV | 1 1/4” | Gas Regulator with SSV | 500 mBar |
RG032-5B-SSV | 1 1/4” | Gas Regulator with SSV | 5 Bar |
RG040-SSV | 1 1/2” | Gas Regulator with SSV | 500 mbar |
RG040-5B-SSV | 1 1/2” | Gas Regulator with SSV | 5 bar |
RG050-SSV | 2" | Gas Regulator with SSV | 500 mbar |
RG050-5B-SSV | 2" | Gas Regulator with SSV | 5 bar |